Leakage current clamp multimeter F65.
Quickly check for leakage currents and look for insulation faults in live plants!
- Analysis of earth leakage circuit breaker tripping currents;
- Earth leakage currents;
- Unbalance currents between phases;
- Strong immunity to adjacent conductor currents;
- Removable anti-harmonic filter to facilitate troubleshooting of disturbed installations;
- 3-year warranty;
- Measurements compatible with VDE 0404-4, VDE 0413-13 and EN 61557-13.
Insulation faults and untimely tripping of earth leakage circuit breakers can sometimes endanger the system and even the user; such phenomena are frequently caused by leakage currents, which are often difficult to detect.
In addition to being the recognised solution for testing and maintenance professionals in industry and the service sector for finding insulation faults, the F65 pocket clamps provide a number of functions found in conventional clamp meters.
Thanks to their exceptional resolution (10 μA) and strong immunity (70 dB) to eddy currents, the F65 clamps are particularly suitable for measuring leakage currents that trigger earth leakage circuit breakers, cause imbalances between phase currents or circulate to earth.
The anti-harmonics filter facilitates the search for these faults on disturbed and power systems (power rectifiers, variable speed drives, inverters...).
The F65 is also a complete clamp multimeter: it measures currents up to 100 A, AC/DC voltage, frequency, resistance and continuity sound signal.
It has a 10000-dot backlit display, display freezing, max and differential (Delta) measurement functions.
To ensure proper autonomy, it has an automatic switch-off in the event of prolonged non-use of the device.
AC amps | Gauges: 60 mA / 600 mA / 10 A / 80 A / 100 A |
Resolution: 10 μA / 100 μA / 1 mA / 10 mA | |
mA accuracy: 2.5 % ± 5 pts (50-500 Hz) 3.5 % ±10 pts (500 Hz-3 kHz) | |
Accuracy A: 2.5 % ± 5 pts (50-500 Hz) 3.5 % ±10 pts (500 Hz-3 kHz) | |
Volts AC | Gauges: 600 V |
Resolution: 0.1 V | |
Accuracy: 1 % ± 5 pts (50-60 Hz); 1.2 % ± 5 pts (50-500 Hz); 2.5 % ± 5 pts (500 Hz-3 kHz) | |
Volt DC | Caibri: 600 V |
Resolution: 0.1 V | |
Accuracy: 1 % ± 2 pts | |
Ohm: | Gauges: 1 kΩ |
Resolution: 0.1 Ω | |
Accuracy: 1 % ± 3 pts (Vmax measurement 3.3 V DC) | |
Continuity test | Buzzer < 35 Ω |
Frequency, AC amps | Gauges: 100 Hz / 1 KHz |
Resolution: 0.1 Hz / 1 Hz | |
Accuracy: 0.5 % ± 2 pts (I > 10 mA) | |
Frequency, DC amps | Gauges: 100 Hz / 1 KHz |
Resolution: 0.1 Hz / 1 Hz | |
Accuracy: 0.5 % ± 2 pts (V > 5 V) | |
Visualisation | 10000 points - 2 measures / s |
Backlighting | Yes |
Maximum value | 100 ms |
Relative measurement | Yes |
Automatic switch-off | Yes, disconnectable |
Opening jaws | 28 mm |
Dimensions | 218 x 64 x 30 mm |
Weight | 280 grams (including batteries) |
Standards | EN 61010-1 / EN 61010-2-032 / EN 61010-2-033 |
Measurement category | CAT III 600 V |
IP Rating | IP30, EN 60529 |
Manufacturer | AMRA Chauvin Arnaux |
Manufacturer code | P01120761 |
Model | F65 |